| SO2048 | |
|---|---|
| Type | MPPT SOLAR CHARGE CONTROLLER | 
| Model | SO2048 | 
| INPUT | |
| Input Voltage Range | 100V ~ 300V (Wide input voltage range) | 
| 180V ~ 260V (Normal input voltage range) | |
| Nominal Input Voltage(s) Supported | 220V AC, 50Hz | 
| Input connection type | Hard Wire | 
| BATTERY Full Load Runtime (minutes) | Depends on Load & Battery AH | 
| No of Battery | 4 | 
| Solar Charge Controller | |
| Type | MPPT/PWM | 
| Max.PV Open Circuit Array Volatge | 88VDC | 
| Charge Algorithm | 3-stage Bulk / Acceptance / Float Plus Equalize | 
| LCD Display | Backlit, Alphanumeric Display showing battery voltage, DC amperage, Cumulative KW hours | 
| OUTPUT | |
| Output Volt Amp Capacity (VA) | 2000 | 
| Output Watt Capacity (watts) | 1600W | 
| DC System Voltage (VDC) | 48V | 
| Load Capacity | >110% faulty after 300ms | 
| Phases | 1Phase – 3 Wire (L.N.E) | 
| Output AC waveform | Pure Sine Wave | 
| Efficiency | > 88% | 
| GENERAL | |
| LCD / LEDs Indications | UPS ON (Yellow), Battery Low (Red), Mains ON (Green),Charging (Green), Overload(Red) | 
| Alarms | Audible alarm indicates power failure and overload conditions | 
| Switches | 1)Switch control off / on power status | 
| 2)Switch for mains input voltage range | |
| 3)Switch to select the maximum charging voltage | |
| Protection | > 300% Load (with manual reset function) | 
| Cooling Method | Forced air cooled | 
| Transfer Time | Battery to line mode : 300 milliseconds / Line to battery mode : 300 milliseconds | 
| Housing Material | Powder coated / painted MS | 
| ENVIRONMENTAL | |
| Operating Temperature Range | 0°C to 50°C | 
| Relative Humidity | 95% (non-condensing) | 
| Degree of Protection | IP 20 | 
| BATTERY | |
| No of Battery | 4 | 
| Battery Charging Profile(Boost /Foat) | Suitable according to Battery type (eg : VRLA/SMF/Wet Lead Acid Battery) | 
| Max Charging Current(when battery is fully discharge) | 10A ±2amp | 
| SPECIAL FEATURES | |
| Cold Start (startup in battery mode during a power failure) | Cold-start operation supported | 
| Charge End Voltage | Grid charging stop when battery reaches 13.8V ±0.2V and transfer to backup mode (per battery) | 
| Grid Recharge Voltage | Grid charging starts when battery reaches 11V ±0.2V and transfer to grid (per battery) | 
| CERTIFICATIONS | |
| Quality Certifications | ISO 9001:2008 | 
| WARRANTY | |
| Product Warranty Period | 1 – year limited warranty | 
| Since we are committed to continuous development of our products, the specification are subject to change without notice. | 
Specifications